ET-2000A
HOME   

 

Earth Resistance Tester ET-2000A
CE

ET-2000A of Pincer Earth Tester, in the measurement of a grounding system with loop,does not require breaking down the grounding wire, and need no auxiliary electrode. It is safe, fast and simple in use.


ET-2000A
 

• In According with GB/T 1.1-2000
• Safe,Fast response and Simple in use

1 Liquid Crystal Display (LCD)
2 Trigger: to control opening and closing of jaw 3 Pincer Jaw : 65 x 32mm
4 POWER Key: Boot Up / Shutdown/ * Quit
5 HOLD Key: lock / Release display
 
Technical Specifications
 
Power Source 6VDC (4 *5# alkaline battery)
Working Temperature -10C -55C
Relative Humidity 10%-90%
LCD 4-digital LCD, 47* 28.5mm in length
Span of Jaw 28mm
Net weight 1160g
Demension(mm) 285* 85 * 56
Protection Level Double insulation
Structural Feature In the jaw way
Shift Automatic
External Magnetic Field < 40A/m
External Electric Field < 1V/m
Measuring Time 1 second
Resistance Measurement Frequency >1KHz
Maximum Resistance Measurement resolution 0.001 O
Range of Resistence Measurement 0.01-200 O
Accessories Carry Case(1),Strap(1), 5# Alkaline Battery

Survey pattern
survey scope
resolution
 
 
accuracy
Resistance
0.010~0.099(O)
0.001(O)
+-(1%+0.01O)
0.10~0.99(O)
0.01(O)
+-(1%+0.01O)
1.0~49.9(O)
0.1(O)
+-(1.5%+0.1O)
50.0~99.5(O)
0.5(O)
+-(2%+0.5O)
100~199(O)
1(O)
+-(3%+1O)
200~395(O)
5(O)
+-(6%+5O)
400~590(O)
10(O)
+-(10%+10O)
600~1000(O)
20(O)
+-(20%+20O)