ET-2000
HOME   
  • Model: ET-2000
    ET- 2000 of Pincer Earth Tester, in the measurement of a grounding system with loop current,does not require breaking down the grounding wire, and need no auxiliary electrode. It is safe, fast and simple in use.


    ET-2000
     

    • In According with GB/T 1.1-2000
    • Safe,Fast response and Simple in use

    1 Liquid Crystal Display (LCD)
    2 Trigger: to control opening and closing of jaw :
    3 Pincer Jaw : 65 x 32mm
    4 POWER Key: Boot Up / Shutdown / * Quit
    5 HOLD Key: lock / Release display
     
    Technical Specifications
     
    Power Source 6VDC (4 x5# alkaline battery)
    Working Temperature -10 C-55 C
    Relative Humidity 10%-90%
    LCD 4-digital LCD, 47* 28.5mm in length
    Span of Jaw 28mm
    Net weight 1160g
    Demension(mm) 285* 85 * 56
    Protection Level Double insulation
    Structural Feature In the jaw way
    Shift Automatic
    External Magnetic Field < 40A/m
    External Electric Field < 1V/m
    Measuring Time 1 second
    Resistance Measurement Frequency > 1KHz
    Maximum Resistance Measurement resolution 0.001 O
    Range of Resistence Measurement 0.01-1000 O
    Accessories Carry Case(1),Strap(1), 5# Alkaline Battery

    Survey pattern
    survey scope
    resolution
     
    accuracy
    Resistance
    0.010~0.099(O)
    0.001(O)
    +-(1%+0.01O)
    0.10~0.99(O)
    0.01(O)
    +-(1%+0.01O)
    1.0~49.9(O)
    0.1(O)
    +-(1.5%+0.1O)
    50.0~99.5(O)
    0.5(O)
    +-(3%+0.5O)
    100~199(O)
    1(O)
    +-(3%+1O)
    200~395(O)
    5(O)
    +-(6%+5O)
    400~590(O)
    10(O)
    +-(10%+10O)
    600~1000(O)
    20(O)
    +-(20%+20O)